Transducer for the conversion of the difference in phase angle from two
electrical systems requiring synchronization into a direct current or voltage
signal which is proportional to the measured value
see also: EURAX 
- Measurement inputs for sinusoidal, square-wave or distorted nominal input
voltages with dominant fundamental wave
- Generator and bus bar input voltage: 10 to 690 V
- Nominal input frequency: 50 Hz
- Auxiliary power: 85 to 230 V AC/DC
- Input frequency response time periods: 4
- Measuring range limits: ± 10° to < ± 180° el
- Measurement output available with unipolar, bipolar or live-zero output
quantities
- Measuring method: acquires distance between zero-crossings
- Power supply: integrated AC-DC power pack with large tolerance range for
universal use
- Standard GL (Germanischer Lloyd) / suitable for use on ocean-going vessels
- Housing:
SINEAX: P13/70 housing for top-hat rail mounting
EURAX: plug-in module (7 standard width units) for 19" rack
- CSA certificate
,
German Lloyd approval 
| Article No. |
Nom. Input Voltage |
Measuring Input |
Output |
| 537-41111110 |
100 V |
-120..0..120°el. |
0.. 20 mA |
| 537-41112110 |
4.. 20 mA |
| 537-41211110 |
230 V |
0.. 20 mA |
| 537-41212110 |
4.. 20 mA |
Order instruments with complete order code (537-4.... ...) in accordance with
the G537 price list. See data sheet for other measuring ranges, inputs,
frequencies, outputs signals and power supplies.
|